Product Finder

50 Hz: 1550 - 3400 kVA
60 Hz: 1125 - 3250 kWe

MTU 4000 DS

  • MTU 4000 DS

    MTU 4000 series generator sets perform at the highest level and cover the power range from 1125 to 3250 kWe (1550 to 3400 kVA). With a robust design and optimal fuel consumption, our diesel generator sets are trusted by customers around the world.

    Verified product design, quality and performance integrity Cutting-edge emissions control Superior on-site specific de-rating behavior due to state-of-theart engine controller with engine site condition management system Compliant with industry codes & standards The generator set fulfills performance per ISO 8528 and offers 100% load acceptance according to NFPA 110 Permanent magnet excitation system for generator as standard for improved transient response Best-in-class reliability and availability Optimized maintenance intervals Fullfil worldwide certifications: ISO 8528, CE/IEC, UL2200, NFPA 110, IBC2009, German Grid Code Uptime Inst. Compliant: Tier I, II, III, IV > Contact

    Industry leading load factor

    85% load factor for standby applications and 75% load factor for prime power applications

    ISO Designed and manufactured

    Our facilities are certified to standards ISO 9001:2008 and ISO 14001:2004

    Advanced monitoring & communications

    Wide range of applications available from island operation to mains parallel operation

    Product list for MTU 4000 DS

    Product

     

    Standby Applications

     

    Prime Applications

       
    Standby Power
    Standby Power with Overload
    Data Center Continuous Power
    Mission Critical Power
     
    Prime Power
    Grid Stability Power
       

    Power output available with varying load for the duration of an emergency outage. Average load factor is <85% for up to 500 h of operating hours per year. No overload capability.

    Load factor is <85% for up to 500 h of operating hours per year. With 10% overload capability for one hour in 12.

    Used in data centers as emergency standby units for the duration of an emergency outage. Load factor is <100% for unlimited operating hours per year. With 10% overload capability for one hour in 12.

    Power output available with varying load for the duration of an emergency outage. Average load factor ≤ 85% for up to 1000 h of operating hours per year. 50Hz: A 10% overload capacity is available for one hour in 12. 60Hz: No overload capability.

     

    Power output available with varying load for unlimited time when grid is not available. Load factor is <75%. With 10% overload capability for one hour in 12.

    Used to stabilize grid when renewable power sources are used or in grid programs like STOR. Load factor is <100% for up to 1000 h of operating hours per year. With 10% overload capability for one hour in 12.

    MTU 12V4000 DS1650

     

    1700 kVA

    1550 kVA

    1550 kVA

    1550 kVA

     

    1550 kVA

    1550 kVA

    MTU 12V4000 DS1750

     

    1800 kVA

    1650 kVA

    1650 kVA

    1650 kVA

     

    1650 kVA

    1650 kVA

    MTU 12V4000 DS2000

     

    2000 kVA

    1850 kVA

    1850 kVA

    1850 kVA

     

    1850 kVA

    1850 kVA

    MTU 16V4000 DS2250

     

    2300 kVA

    2100 kVA

    2100 kVA

    2100 kVA

     

    2100 kVA

    2100 kVA

    MTU 16V4000 DS2500

     

    2600 kVA

    2250 kVA

    2250 kVA

    2250 kVA

     

    2250 kVA

    2250 kVA

    MTU 20V4000 DS2750

     

    2700 kVA

    2600 kVA

    2600 kVA

    2600 kVA

     

    2600 kVA

    2600 kVA

    MTU 20V4000 DS3100

     

    3200 kVA

    2850 kVA

    2850 kVA

    2850 kVA

     

    2850 kVA

    2850 kVA

    MTU 20V4000 DS3300

     

    3400 kVA

    3100 kVA

    3100 kVA

    3100 kVA

     

    3100 kVA

    3100 kVA

    Product

     

    Standby Applications

       
    Standby Power
    Standby Power with Overload
    Data Center Continuous Power
    Mission Critical Power
       

    Power output available with varying load for the duration of an emergency outage. Average load factor is <85% for up to 500 h of operating hours per year. No overload capability.

    Load factor is <85% for up to 500 h of operating hours per year. With 10% overload capability for one hour in 12.

    Used in data centers as emergency standby units for the duration of an emergency outage. Load factor is <100% for unlimited operating hours per year. With 10% overload capability for one hour in 12.

    Power output available with varying load for the duration of an emergency outage. Average load factor ≤ 85% for up to 1000 h of operating hours per year. 50Hz: A 10% overload capacity is available for one hour in 12. 60Hz: No overload capability.

    MTU 12V4000 DS1650

     

    1700 kVA

    1550 kVA

    1550 kVA

    1550 kVA

    MTU 12V4000 DS1750

     

    1800 kVA

    1650 kVA

    1650 kVA

    1650 kVA

    MTU 12V4000 DS2000

     

    2000 kVA

    1850 kVA

    1850 kVA

    1850 kVA

    MTU 16V4000 DS2250

     

    2300 kVA

    2100 kVA

    2100 kVA

    2100 kVA

    MTU 16V4000 DS2500

     

    2600 kVA

    2250 kVA

    2250 kVA

    2250 kVA

    MTU 20V4000 DS2750

     

    2700 kVA

    2600 kVA

    2600 kVA

    2600 kVA

    MTU 20V4000 DS3100

     

    3200 kVA

    2850 kVA

    2850 kVA

    2850 kVA

    MTU 20V4000 DS3300

     

    3400 kVA

    3100 kVA

    3100 kVA

    3100 kVA

    Product

     

    Prime Applications

       
    Prime Power
    Grid Stability Power
       

    Power output available with varying load for unlimited time when grid is not available. Load factor is <75%. With 10% overload capability for one hour in 12.

    Used to stabilize grid when renewable power sources are used or in grid programs like STOR. Load factor is <100% for up to 1000 h of operating hours per year. With 10% overload capability for one hour in 12.

    MTU 12V4000 DS1650

     

    1550 kVA

    1550 kVA

    MTU 12V4000 DS1750

     

    1650 kVA

    1650 kVA

    MTU 12V4000 DS2000

     

    1850 kVA

    1850 kVA

    MTU 16V4000 DS2250

     

    2100 kVA

    2100 kVA

    MTU 16V4000 DS2500

     

    2250 kVA

    2250 kVA

    MTU 20V4000 DS2750

     

    2600 kVA

    2600 kVA

    MTU 20V4000 DS3100

     

    2850 kVA

    2850 kVA

    MTU 20V4000 DS3300

     

    3100 kVA

    3100 kVA

    Product

     

    Standby Applications

     

    Prime Applications

       
    Standby Power
    Data Center Continuous Power
     
    Prime Power
       

    Power output available with varying load for the duration of an emergency outage. Average load factor is <85% for up to 500 h of operating hours per year. No overload capability.

    Used in data centers as emergency standby units for the duration of an emergency outage. Load factor is <100% for unlimited operating hours per year. With 10% overload capability for one hour in 12.

     

    Power output available with varying load for unlimited time when grid is not available. Load factor is <75%. With 10% overload capability for one hour in 12.

    North and Latin America

    MTU 12V4000 DS1250

     

    1250 kWe

    1135 kWe

     

    1125 kWe

    MTU 12V4000 DS1500

     

    1500 kWe

    1400 kWe

     

    1400 kWe

    MTU 12V4000 DS1750

     

    1750 kWe

    1600 kWe

     

    1600 kWe

    MTU 16V4000 DS2000

     

    2000 kWe

    1825 kWe

     

    1800 kWe

    MTU 16V4000 DS2250

     

    2250 kWe

    2045 kWe

     

    2045 kWe

    MTU 16V4000 DS2500

     

    2500 kWe

    --

     

    --

    MTU 20V4000 DS2500

     

    2500 kWe

    2275 kWe

     

    2250 kWe

    MTU 20V4000 DS2800

     

    2800 kWe

    2500 kWe

     

    2500 kWe

    MTU 20V4000 DS3000

     

    3000 kWe

    2800 kWe

     

    2800 kWe

    MTU 20V4000 DS3250

     

    3250 kWe

    --

     

    --

    Europe, Africa, Asia and Australia

    MTU 12V4000 DS1550

     

    1550 kWe

    --

     

    --

    MTU 16V4000 DS2050

     

    2070 kWe

    --

     

    --

    MTU 20V4000 DS3250

     

    3250 kWe

    --

     

    --

    Product

     

    Standby Applications

       
    Standby Power
    Data Center Continuous Power
       

    Power output available with varying load for the duration of an emergency outage. Average load factor is <85% for up to 500 h of operating hours per year. No overload capability.

    Used in data centers as emergency standby units for the duration of an emergency outage. Load factor is <100% for unlimited operating hours per year. With 10% overload capability for one hour in 12.

    North and Latin America

    MTU 12V4000 DS1250

     

    1250 kWe

    1135 kWe

    MTU 12V4000 DS1500

     

    1500 kWe

    1400 kWe

    MTU 12V4000 DS1750

     

    1750 kWe

    1600 kWe

    MTU 16V4000 DS2000

     

    2000 kWe

    1825 kWe

    MTU 16V4000 DS2250

     

    2250 kWe

    2045 kWe

    MTU 16V4000 DS2500

     

    2500 kWe

    --

    MTU 20V4000 DS2500

     

    2500 kWe

    2275 kWe

    MTU 20V4000 DS2800

     

    2800 kWe

    2500 kWe

    MTU 20V4000 DS3000

     

    3000 kWe

    2800 kWe

    MTU 20V4000 DS3250

     

    3250 kWe

    --

    Europe, Africa, Asia and Australia

    MTU 12V4000 DS1550

     

    1550 kWe

    --

    MTU 16V4000 DS2050

     

    2070 kWe

    --

    MTU 20V4000 DS3250

     

    3250 kWe

    --

    Product

     

    Prime Applications

       
    Prime Power
       

    Power output available with varying load for unlimited time when grid is not available. Load factor is <75%. With 10% overload capability for one hour in 12.

    North and Latin America

    MTU 12V4000 DS1250

     

    1125 kWe

    MTU 12V4000 DS1500

     

    1400 kWe

    MTU 12V4000 DS1750

     

    1600 kWe

    MTU 16V4000 DS2000

     

    1800 kWe

    MTU 16V4000 DS2250

     

    2045 kWe

    MTU 16V4000 DS2500

     

    --

    MTU 20V4000 DS2500

     

    2250 kWe

    MTU 20V4000 DS2800

     

    2500 kWe

    MTU 20V4000 DS3000

     

    2800 kWe

    MTU 20V4000 DS3250

     

    --

    Europe, Africa, Asia and Australia

    MTU 12V4000 DS1550

     

    --

    MTU 16V4000 DS2050

     

    --

    MTU 20V4000 DS3250

     

    --

    Options for MTU 4000 DS

    Control Panel

    Wide variety of control panel configuration; full range of applications from island operation to mains parallel operation of multiple gensets; various expansion modules (analog and digital in- and outputs) for controller

    Fuel System

    Fuel pre-filters with water separators

    Exhaust system

    Silencers from varying sound attenuation levels

    > CONTACT

    Register for our Newsletter

    Subscribe to our MTU eReport and stay up to date with news and stories around our brands MTU Onsite Energy and MTU.

    > Subscribe here